Start from the steel warehouse model (free sign-up). Japan’s Fire Service Act Order asks a warehouse (Appended Table 1, item 14) for extinguishers from 150 m² of total floor (Article 10(1)(ii)) and an automatic fire alarm from 500 m² (Article 21(1)(iv)). In this article, in the members’ steel warehouse (1,484.04 m² in all, a 6 m ceiling), your AI puts in extinguishers and checks them, and counts the detectors. It ran the same tools an AI calls over MCP. Every figure and number below comes from that run.

1. The extinguishers

Your AI checks with check_space’s extinguishers. At 1,484.04 m², 150 m² or more, the warehouse needs extinguishers. Article 6 of the Fire Service Act Rules asks a warehouse for one unit for each 100 m²: 14.84 units. This one is a quasi-fire-resistant building whose main structure is not fire-resistant, so the area does not double.

  • Your AI puts five extinguishers of three units each (15 units) spread along the walls: on the west, north and east walls and two on the south (edit_space).
  • Checked for a walk of 20 m at most from anywhere on the floor to the nearest, the office’s north-west corner is 20.27 m away: too far. It is the walk through the office door to the west wall’s extinguisher.
  • In one change your AI moves the west wall’s extinguisher 2 m north. The farthest point is then 18.75 m: within 20 m.
Plan of the warehouse with the five extinguishers
Four indoor fire hydrants and five extinguishers on the walls

2. The fire alarm’s detectors

At 500 m² or more, the warehouse needs an automatic fire alarm. Your AI counts the detectors with check_space’s fireAlarm.

  • Counted on the model’s zones (the storage, the staging area and the office), 18 smoke detectors. But the floor without racks south and east of the office (197.65 m²) is in none of them.
  • Outside the office the warehouse is one detection area with no walls between, so your AI draws its floor less the office as one zone (1,408.57 m²).
DetectorsWarehouse floor (6 m ceiling)Office (2.7 m ceiling)In all
Smoke (class 2)19 (one for each 75 m²)1 (150 m²)20
Differential heat (class 1)47 (30 m²)2 (50 m²)49
Differential heat (class 2)57 (25 m²)2 (40 m²)59
  • With the ceiling 4 m or higher, a smoke detector covers 75 m². A heat detector covers less where the main structure is not fire-resistant, so it takes more than twice as many as smoke.

3. Using the check