Start from the office building model (free sign-up), or draw your own. In Japan a building must appoint a fire prevention manager once its occupant capacity reaches a threshold. An office's occupant capacity grows not only with its staff but with the floor area its visitors use, and with a shop in the same building the threshold itself moves. Here an AI counted whether a model three-storey office building needs one, with the same tools it calls over MCP. Every figure below is their result.

1. The rules

  • The threshold. An office (item (15) of Appended Table 1 of the Order for Enforcement of the Fire Service Act, the Fire Service Act Order) needs a fire prevention manager from an occupant capacity of 50 (Article 1-2(3)(i)(c) of the Order); a building of mixed uses with a restaurant or a shop in it (item (16)(a)) needs one from 30 (Article 1-2(3)(i)(b)).
  • The occupant capacity. An office counts its staff plus one person per 3 m² of the areas used mainly by people who are not staff (Article 1-3 of the Regulation for Enforcement of the Fire Service Act). The staff are the most on duty at one time on an ordinary day.
  • Class A or Class B course. For an office under 500 m² in total (under 300 m² for item (16)(a) and the like), a manager who has taken the Class B course will do; above that, the Class A course is required (Article 3 of the Order).

2. What was done

  • The model is a three-storey office building of 21 × 15 m, 923.52 m² in total (the same as in the extinguishers article).
  • The AI counted the building's occupant capacity with check_space: as an office alone (no other use in the building) with 40, 49 and 50 staff; with 41 staff and the ground floor's meeting room used as a reception for visitors; and with a restaurant on one floor (an occupant capacity of 25, assumed) and 10 office staff.

3. What it found

CaseOccupant capacityThresholdFire prevention manager
40 staff4050Not needed
49 staff4950Not needed
50 staff5050Needed (Class A course)
41 staff + the ground floor's meeting room as a reception5050Needed (Class A course)
10 staff + a restaurant (25) on the ground floor3530Needed (Class A course)
  • By staff alone, from 50. With 49 staff the office building needs no fire prevention manager; with 50 staff it needs one.
  • Rooms for visitors count. Used as a reception for visitors, the ground floor's meeting room (29.64 m²) adds 29.64 ÷ 3 = 9.88, rounded down to 9: with 41 staff the total is 50, so a manager is needed. Used only for the staff's own meetings, it does not count.
  • A shop in the building lowers the threshold to 30. A building with a restaurant in it is item (16)(a), and its threshold depends on the occupant capacity of the whole building: 10 office staff and the restaurant's 25 make 35, so a manager is needed.
  • Each needs the Class A course. 923.52 m² in total is over the office's 500 m² and item (16)(a)'s 300 m².
Plan of the office building's ground floor
Plan of the office building's ground floor

4. How to ask an AI

This is a three-storey office building of 923.52 m² in total. At most 45 staff are on duty at one time, and the meeting room on the ground floor is used to receive visitors. Check whether it needs a fire prevention manager, and whether the manager needs the Class A or the Class B course.

5. What this does not check

  • The reception's floor area is its drawn room (inside the walls). Measured to the walls' centres it is 31.40 m², 10 people (51 with 41 staff: the same answer).
  • How a building whose control is divided (let to several tenants) appoints its managers, and the overall fire prevention manager, are not covered.
  • What follows the appointment: the notification, the fire prevention plan and the drills.
  • In the end, ask the local fire department.