Start from the office building model (free sign-up), or draw your own. For an office's extinguishers, Japan's fire code sets not only how many but where: every part of each floor must be within a 20 m walk, measured round the desks and partitions, which a ruler on the plan does not give. Here an AI checked how many extinguishers a model three-storey office building needs and where they must go, with the same tools it calls over MCP. Every figure and drawing below is their result.

1. The rules

  • Whether they are needed. An office (item (15) of Appended Table 1 of the Order for Enforcement of the Fire Service Act, the Fire Service Act Order) with a total floor area of 300 m² or more needs extinguishers or the like (Article 10(1)(iii) of the Order). Under 300 m², a basement, a "windowless floor" (a floor without enough openings for firefighting) or floor 3 and above still needs them if it has 50 m² or more (Article 10(1)(v)).
  • Extinguisher units. The extinguisher units on the labels (Japan's rating of an extinguisher's capacity: 3 for an A-3), added up, must reach the total floor area ÷ 200 m² (Article 6(1) of the Regulation for Enforcement of the Fire Service Act, the Fire Service Act Regulation), or ÷ 400 m² for a building whose main structure is fire-resistant and whose walls and ceilings are finished in flame-retardant materials (Article 6(2)).
  • Where. On each floor, every part must be within a 20 m walk of an extinguisher (Article 6(6) of the Regulation), placed at most 1.5 m above the floor (Article 9 of the Regulation).

2. What was done

  • The model is a three-storey office building of 21 × 15 m (the same as in the automatic fire alarm article): each floor 307.84 m², 923.52 m² in total. Along the north are the stair hall, the toilets, the kitchenette and the meeting room (a document store on floor 3); across the corridor, the office with eight islands of desks runs along the south. There is one stair, in the north-west corner. Floors are counted as in Japan, the ground floor being floor 1.
  • No extinguisher is drawn. The AI checked each floor with the extinguisher check of check_space (an office of 923.52 m² in total, each extinguisher of 3 units, assumed; the walk goes round the desk islands too).
  • Then it put one extinguisher on each floor in the stair hall by the corridor (edit_space) and checked; last, it moved the three to the middle of the corridor, against the office's wall, and checked again.

3. How many

With 923.52 m² in total, 300 m² or more, the whole building needs them (Article 10(1)(iii)). The units: 923.52 ÷ 200 = 4.62 or more, or 923.52 ÷ 400 = 2.31 or more if fire-resistant with flame-retardant finishes. One extinguisher of 3 units on each floor gives 9 units in total, enough for the 4.62 units needed.

4. Where

WhereGround floorFloor 2Floor 3
In the stair hall by the corridor20.12 m (over 20 m)20.12 m (over 20 m)20.12 m (over 20 m)
In the middle of the corridor16.59 m16.47 m16.47 m

The walk from each floor's farthest point to the nearest extinguisher (accurate to within ±0.06 m).

Floor 3: the extinguisher in the stair hall and the walk of 20.12 m from the office's south-east corner
Floor 3: the extinguisher in the stair hall and the walk of 20.12 m from the office's south-east corner
  • One by the stair is just over 20 m on every floor. The farthest point is the office's south-east corner: the walk goes round the desk islands and out by the west door to the stair hall, 20.12 m, over 20 m even allowing for the ±0.06 m.
  • In the middle of the corridor, every floor is within 20 m. The farthest point is along the office's south wall, a little west of the middle: 16.47 m through the office's door (16.59 m on the ground floor, from the south entrance). It is still three extinguishers.
Floor 3: the extinguisher moved to the middle of the corridor and the walk of 16.47 m from along the office's south wall
Floor 3: the extinguisher moved to the middle of the corridor and the walk of 16.47 m from along the office's south wall
  • Either way the tops of the extinguishers are 0.6 m up, within 1.5 m, and check_space found no issues.

5. How to ask an AI

This is a three-storey office building of 923.52 m² in total, with A-3 extinguishers (3 units). Check how many it needs and where on each floor to put them so that every part is within a 20 m walk, round the desks.

6. What this does not check

  • The kind of extinguisher (powder, liquid and so on), and the extra ones needed where there is electrical equipment or a small amount of hazardous material (Article 6 of the Regulation).
  • The signs for the extinguishers, and their inspection and reporting.
  • The walk goes round the walls, doors and desk islands that are drawn; furniture or goods not drawn are not counted.
  • In the end, ask the local fire department.