Japan's Order for Enforcement of the Building Standards Act sets how far a habitable room may be from a direct stair (a stair that leads straight to the evacuation floor, the floor with a door straight out to the ground) in Article 120, which floors need two direct stairs or more in Article 121, and how wide a shop's exits must be in Article 125(3). Here are seven buildings an AI checked in earlier articles (floors are counted as in Japan, the ground floor being floor 1). The tool the AI calls over MCP (check_space, its walking-distance check) measures the walk from a room's farthest point to the edge of a stair, round walls, columns and furniture and through the doors.

1. How far from a stair (Article 120)

RoomQuasi-fire-resistant or non-combustible structureOtherwise
Windowless rooms, and the main rooms of shops, restaurants and the like30 m30 m
The main rooms of hospitals, clinics with beds, hotels, flats, welfare facilities and the like50 m30 m
Other rooms50 m40 m
  • Quasi-noncombustible finishes in the rooms and in the corridors and stairs to the ground add 10 m; on floor 15 and above, the limit is 10 m less without them (Article 120(2) and (3)).
BuildingRoomFrom the farthest point to a stairLimit
A restaurant on floor 3 of a buildingPrivate room 331.44 m30 m
A restaurant on floor 3 of a buildingThe dining room16.17 m30 m
A clinic's ward floor (one stair)Ward A36.57 m50 m
A clinic's ward floor (an outside stair added)The farthest ward, to the nearer stair20.31 m50 m
A business hotel's guest floorThe farthest room, to the nearer stair18.31 m50 m
A business hotel's guest floorThe east stair only30.84 m50 m
A nursery on floor 3 of a buildingThe farthest playroom, to the nearer stair17.02 m30 m
  • The nursery's limit of 30 m, from each part of the children's rooms to a stair, comes from Japan's Standards for the Equipment and Operation of Child Welfare Facilities, Article 32(viii).
  • A single-storey nursery has every playroom within 8.72 m of a door to its yard; with the front door only, the five-year-olds' room is 36.46 m from it (to a way out).
The business hotel's guest floor: an evacuation route map
Each room's walk to the nearer stair

2. Two direct stairs (Article 121)

BuildingFloorFloor area countedLine (quasi-fire-resistant or better)Two needed
A three-storey office buildingFloor 2's rooms (just above the evacuation floor)219.64 m²200 m² (400 m²)Yes (not if quasi-fire-resistant or better)
A three-storey office buildingFloor 3's rooms (a document store in place of a meeting room)188.24 m²100 m² (200 m²)Yes (not if quasi-fire-resistant or better)
A three-storey office buildingFloor 3's rooms (with a meeting room)219.64 m²100 m² (200 m²)Yes (even if quasi-fire-resistant or better)
A clinic's ward floorWards136.16 m²50 m² (100 m²)Yes (either way)
A nursery on floor 3 of a buildingChildren's rooms and the like113.04 m²50 m² (100 m²)Yes (either way)
  • The business hotel's guest floor (floor 5) needs two direct stairs, because its guest rooms, 240.91 m² in all, are over 200 m² (the line for quasi-fire-resistant or better).
  • For the clinic, the Enforcement Regulations on the Medical Care Act, Article 16(1)(viii), allows one indoor direct stair if patients have a lift; Article 121 has no such exception.

3. A shop's exits (Article 125(3))

ShopIts largest floorWidth neededWidth it has
A street shop155.04 m²0.94 m2 m
A convenience store272.06 m²1.64 m2.8 m
A drugstore852.04 m²5.12 m3.3 m
A drugstore (a 2 m fire exit added)852.04 m²5.12 m5.3 m
A supermarket (the published example)5,909.48 m²35.46 m10.6 m
A supermarket (15 fire exits of 1.8 m added)5,909.48 m²35.46 m37.6 m
  • A shop selling goods needs exits to the outside on its evacuation floor at least 60 cm wide in all per 100 m² of its largest floor.

4. The articles

5. How to ask an AI

On this floor (as drawn, a restaurant on floor 3 of a three-storey building, quasi-fire-resistant), how far is the walk from each room's farthest point to the stair? If a room is over 30 m, how could it come within the limit? Does the floor need two direct stairs?

6. What this does not check

  • Whether a stair is a direct stair (one that runs to the evacuation floor or the ground) is for the drawing to say. Escape stairs, special escape stairs, and the stretch where the walks to two stairs overlap are not covered.
  • The floor areas are as each article counted them (the office building's to the centres of the walls, the clinic's the areas drawn for the rooms). For a final answer, ask the building control authority.