Whether a building needs extinguishers, how many and where are set by Article 10 of Japan's Order for Enforcement of the Fire Service Act (in Japanese; the Fire Service Act Order) and Article 6 of the Regulation for Enforcement of the Fire Service Act (in Japanese; the Fire Service Act Regulation). They depend on the thresholds of total floor area, the extinguisher units (Japan's rating of an extinguisher's capacity) and the 20 m walk. Here are eleven facilities an AI checked in earlier articles with the extinguisher check of check_space, the tool it calls over MCP. The convenience store's drawing has the shop and its car park on one floor; the check counts the shop its outer walls enclose as the floor.

1. The rules

Use (Appended Table 1 of the Fire Service Act Order)NeededOne unit for
(1)(a) theatres, (2) cabarets, arcades and karaoke, (6)(a)1–3 hospitals and clinics with beds, (6)(b) care homes and the likeWhatever the floor area50 m² ((6): 100 m²)
(3) restaurants with equipment that uses fire (without safety devices)Whatever the floor area100 m²
(1)(b) assembly halls and wedding venues, (3) restaurants, (4) shops and exhibition halls, (5) hotels and flats, (6)(a)4, (c) and (d) clinics, nurseries and kindergartens, (9) baths, (12)–(14) factories, garages and warehousesFrom 150 m² in total100 m²
(7) schools, (8) libraries, (10) stations, (11) shrines and temples, (15) offices and the likeFrom 300 m² in total200 m²
Any other floorA basement, a windowless floor or floor 3 and above, from 50 m² of floor areaThe use's
  • Units. At least the total floor area (or the floor's own area, where the floor alone triggers the rule) divided by the use's area (Article 6 of the Regulation); twice the area if fire-resistant with flame-retardant finishes.
  • Where. On each floor, every part must be within a 20 m walk of one (Article 6(6) of the Regulation).
  • Floors are counted as in Japan, the ground floor being floor 1. A "windowless floor" is a floor without enough openings for firefighting.

2. Eleven facilities

Facility (use)Total floor areaExtinguishersUnits
A banquet hall for 200 ((1)(b))1,262.06 m²Needed12.62 or more
An exhibition hall ((4))920.56 m²Needed9.21 or more
A convenience store ((4))272.06 m²Needed2.72 or more
An orthopaedic clinic ((6)(a)4)300.84 m²Needed3.01 or more
An internal medicine clinic ((6)(a)4)271.56 m²Needed2.72 or more
An animal hospital ((15))210.04 m²Not needed―
A clinic for human patients, the same size ((6)(a)4)210.04 m²Needed2.1 or more
A 24-hour gym ((15))327.24 m²Needed1.64 or more
A three-storey office building ((15))923.52 m²Needed4.62 or more
A hair salon ((15)), ground floor56 m²Not needed―
A hair salon ((15)), floor 356 m²Needed (floor 3, 50 m² or more)0.28 or more
A small nursery ((6)(c)), ground floor121.44 m²Not needed―
A small nursery ((6)(c)), floor 3121.44 m²Needed (floor 3, 50 m² or more)1.21 or more
A small café ((3)(b)) with equipment that uses fire60.84 m²Needed (whatever its floor area)0.61 or more
A small café ((3)(b)) with safety devices60.84 m²Not needed―
  • The use sets the threshold. Offices and animal hospitals ((15)) need them from 300 m², so an animal hospital of 210.04 m² needs none; a clinic for human patients with the same 210.04 m² is (6)(a)4, from 150 m².
  • Floor 3 depends on the floor itself. A hair salon (56 m²) and a small nursery (121.44 m²) need none on the ground floor but need them on floor 3, from 50 m² of floor area.
  • A restaurant that uses fire. Even a small café needs them, whatever its floor area, if it has a gas hob or other equipment that uses fire without safety devices.

3. Where: within 20 m

FacilityPlacedFarthest pointPlaced againFarthest point
An exhibition hallFour by the doors21.78 mOne more on the north wall, five18.16 m
An office buildingOne on each stair hall20.12 mIn the middle of the corridor16.59 m
  • Enough units can still be placed too far away. In the exhibition hall, four extinguishers by the doors give 12 units (enough for 9.21), yet the back of a booth in the north row is 21.78 m from one.
Plan of the exhibition hall: with five extinguishers, the walk from the farthest point to one
One more on the north wall: 18.16 m from the farthest point

4. The articles

5. How to ask an AI

Does this shop (as drawn, a shop of 270 m² in all) need extinguishers? If so, how many units, and where must they go so every part is within 20 m walking of one?

6. What this does not check

  • Small quantities of hazardous materials or designated combustibles, and the extra extinguishers for boiler and electrical rooms (Article 6(3) to (5) of the Regulation), are not covered.
  • The total floor areas are measured to the walls' centres. In a building of tenancies, a business's part counts as a building of its own (Article 9 of the Order). In the end, ask the local fire department.